Innerduct

SCHEDULE 40 & SCHEDULE 80
TC6-EB & TC8-DB
CERTACOM
C-DUCT TELECOM

SCHEDULE 40 & SCHEDULE 80

In compliance with the industry standards, Our PVC Electrical Conduit is manufactured from virgin PVC compounds complying with the UL 651 standards and as described in standard specifications for rigid PVC compounds ASTM D 1784-81. Our PVC Electrical Conduits are subject to in-process quality control to assure compliance with appropriate manufacturing and performance standards.

PVC Electrical Conduit & Accessories meet the requirements and adhere to the appropriate UL listing & labels as established by:

  • Underwriters Laboratories (UL) Standard 651 (Conduit)
  • RUS Listed
  • NEMA TC-2 (Accessories)
  • NEMA TC-3 (Accessories)
  • UL Standard 514B (Accessories)
  • General Service Administration (GSA) WC-1094A
  • National Electrical Code – Article 347
  • Underwriters Laboratories, Inc., E-97809

Applications: underground, encased in concrete for direct burial. Also for use in sunlight and weather exposed or concealed applications above ground.

  • Sunlight and weather resistant
  • Reduced emissions of smoke and HCL
  • Listed for 90 degree C conductors or cable and direct
    sunlight
  • Rigid nonmetallic raceway for wires and cables in accordance with the NEC
  • Superior weathering characteristics
 

SCHEDULE 40

10 FOOT PART # 20 FOOT PART # NOMINAL SIZE WEIGHT 100 FEET CRATE QTY 10' LENGTHS O.D. I.D. WALL
51051 51052 1/2" 16.4 6000' .840 .622 .109
51071 51072 3/4" 21.8 4400' 1.050 .824 .113
51101 51102 1" 32.1 3600' 1.315 1.049 .133
51131 51132 1 1/4" 43.4 3300' 1.660 1.380 .140
51151 51152 1 1/2" 51.8 2250' 1.900 1.610 .145
51201 51202 2" 69.5 1400' 2.375 2.067 .154
51251 51252 2 1/2" 109.6 930' 2.875 2.469 .203
51301 51302 3" 143.5 880' 3.500 3.068 .216
51351 51352 3 1/2" 169.1 630' 4.000 3.548 .226
51401 51402 4" 204.3 570' 4.500 4.026 .237
51501 51502 5" 277.6 380' 5.563 5.047 .258
51601 51602 6" 360.0 260' 6.625 6.065 .280

SCHEDULE 80

10 FOOT PART # 20 FOOT PART # NOMINAL SIZE WEIGHT 100 FEET CRATE QTY 10' LENGTHS O.D. WALL
58051 58052 1/2" 20.5 6000' .840 .147
58071 58072 3/4" 27.8 4400' 1.050 .154
58101 58102 1" 40.9 3600' 1.315 .179
58131 58132 1 1/4" 56.7 3300' 1.660 .191
58151 58152 1 1/2" 68.6 2250' 1.900 .200
58201 58202 2" 94.9 1400' 2.375 .218
58251 58252 2 1/2" 144.9 930' 2.875 .276
58301 58302 3" 193.8 880' 3.500 .300
58351 58352 3 1/2" 234.5 630' 4.000 .318
58401 58402 4" 283.3 570' 4.500 .337
58501 58502 5" 393.8 380' 5.563 .375
58601 58602 6" 541.1 260' 6.625 .432

TC6-EB & TC8-DB

Applications
  • Power Utility Primary
  • Power Utility Secondary
  • Street Lighting
Meets and Exceeds
  • NEMA TC-6
  • NEMA TC-8
  • ASTM F-512
  • ASTM D-1784
  • RUS Listed

500,000 PSI MODULUS

TC-6
TYPE DB-60 DUCT (For Direct Burial or Concrete Encasement)

20 FOOT PART # NOMINAL SIZE WEIGHT/ 100 FEET CRATE QTY 20' O.D. WALL
53202 2" 33.7 2800 2.375 .060
53302 3" 73.4 1760 3.500 .092
53402 4" 121.8 1140 4.500 .121
53502 5" 184.6 760 5.563 .152
53602 6" 263.4 520 6.625 .182

TC-8
TYPE DB-120 DUCT (For Direct Burial or Concrete Encasement)

20 FOOT PART # NOMINAL SIZE WEIGHT/ 100 FEET CRATE QTY 20' O.D. WALL
55102 1" 16.9 7200 1.315 .060
55152 1 1/2" 24.7 4500 1.900 .065
55202 2" 42.7 2800 2.375 .077
55302 3" 91.0 1760 3.500 .118
55402 4" 150.2 1140 4.500 .154
55502 5" 232.5 760 5.563 .191
55602 6" 331.6 520 6.625 .227

TC-6
TYPE EB-20 DUCT (For Concrete Encasement Only)

20 FOOT PART # NOMINAL SIZE WEIGHT/ 100 FEET CRATE QTY 20' O.D. WALL
54202 2" 33.7 2800 2.375 .060
54302 3" 54.7 1760 3.500 .061
54402 4" 90.1 1140 4.500 .082
54502 5" 139.7 760 5.563 .103
54602 6" 196.9 520 6.625 .125

TC-8
TYPE EB-35 DUCT (For Concrete Encasement Only)

20 FOOT PART # NOMINAL SIZE WEIGHT/ 100 FEET CRATE QTY 20' O.D. WALL
56202 2" 33.7 2800 2.375 .060
56302 3" 58.4 1760 3.500 .076
56402 4" 101.7 1140 4.500 .100
56502 5" 158.6 760 5.563 .126
56602 6" 221.0 520 6.625 .152

TYPE DB-100

20 FOOT PART # NOMINAL SIZE WEIGHT/ 100 FEET CRATE QTY 20' O.D. WALL
57302 3" 85.3 1760 3.500 .112
57402 4" 141.9 1140 4.500 .145
57502 5" 216.5 760 5.553 .179
57602 6" 307.0 520 6.625 .213

400,000 PSI MODULUS

TC-6
TYPE DB-60 DUCT (For Direct Burial or Concrete Encasement)

20 FOOT PART # NOMINAL SIZE WEIGHT/ 100 FEET CRATE QTY 20' O.D. WALL
53202LM 2" 33.7 2800 2.375 .065
53302LM 3" 73.4 1760 3.500 .100
53402LM 4" 121.8 1140 4.500 .131
53502LM 5" 184.6 760 5.563 .164
53602LM 6" 263.4 520 6.625 .196

TC-8
TYPE DB-120 DUCT (For Direct Burial or Concrete Encasement)

20 FOOT PART # NOMINAL SIZE WEIGHT/ 100 FEET CRATE QTY 20' O.D. WALL
55102LM 1" 16.9 7200 1.315 .060
55152LM 1 1/2" 24.7 4500 1.900 .065
55202LM 2" 42.7 2800 2.375 .083
55252LM 2 1/2" 60.4 1860 2.875 .105
55302LM 3" 91.0 1760 3.500 .127
55402LM 4" 150.2 1140 4.500 .166
55502LM 5" 232.5 760 5.563 .205
55602LM 6" 331.6 520 6.625 .244

TC-6
TYPE EB-20 DUCT (For Concrete Encasement Only)

20 FOOT PART # NOMINAL SIZE WEIGHT/ 100 FEET CRATE QTY 20' O.D. WALL
54202LM 2" 33.7 2800 2.375 .060
54302LM 3" 54.7 1760 3.500 .067
54402LM 4" 90.1 1140 4.500 .089
54502LM 5" 139.7 760 5.563 .112
54602LM 6" 196.9 520 6.625 .135

TC-8
TYPE EB-35 DUCT (For Concrete Encasement Only)

20 FOOT PART # NOMINAL SIZE WEIGHT/ 100 FEET CRATE QTY 20' O.D. WALL
56202LM 2" 33.7 2800 2.375 .060
56302LM 3" 58.4 1760 3.500 .082
56402LM 4" 101.7 1140 4.500 .109
56502LM 5" 158.6 760 5.563 .136
56602LM 6" 221.0 520 6.625 .164

TYPE DB-100

20 FOOT PART # NOMINAL SIZE WEIGHT/ 100 FEET CRATE QTY 20' O.D. WALL
57302LM 3" 85.3 1760 3.500 .121
57402LM 4" 141.9 1140 4.500 .155
57502LM 5" 216.5 760 5.553 .192
57602LM 6" 307.0 520 6.625 .229

CERTACOM

All the Advantages of the Contractor-Proven Certa-Lok™ PVC Joining System
  • Lightweight and easy to handle
  • Corrosion-resistant
  • Engineered joint immediately achieves full strength in all weather conditions
  • No solvent-cements required
Now available for the trenchless construction market!
  • Eliminates the cost, handling and assembly problems associated with HDPE pipe
  • 20′ and 10′ lengths facilitate rapid assembly and eliminate right-of-way requirements

CertainTeed developed the splinelock joining system thirty years ago, and has successfully applied this technology in many demanding applications, including mining, irrigation, water well and trenchless water distribution systems. Put this experience to work for you in your next trenchless raceway project

Dimensions, Weights and Performance Data

SIZE O.D. T, MIN. I.D. @ MIN. WALL MAX. TENSILE PULL (NOTE 1) APPROX. WEIGHT LBS./FT. BOD C X W D MIN./MAX. P
4" SCH40 4.500" 0.237" 4.026" 8700 lbs. 2.06 5.02" 4.25" 3.000" 0.375" .125"/.130" 0.25"

Packaging

SIZE PART NO. FT. PER FAST-PAK FAST-PAKS PER TRUCKLOAD FEET PER TRUCKLOAD
4" SCH40 66703 580 28 16,240

Accessories

SIZE EXTRA SPLINES EXTRA O-RINGS
PART NO. LENGTH CROSS-SECTION PART NO. CROSS-SECTION
4" SCH40 86462 18" .250" ROUND 86123 0.210"

C-DUCT TELECOM

PRODUCT NUMBER DESCRIPTION O.D. WALL WEIGHT PER FOOT FEET PER LIFT
17402 4" Type B Encased Burial 4.350 0.095 0.930 1260'
18402 4" Type C Direct Burial 4.350 0.150 1.500 1260'
19402 4" Type D Exposed Application 4.350 0.150 1.500 1260'

Note:
(1) Meets specifications of Bell operating companies
(2) Meets requirements of NEMA TC-10 for C and B
(3) Type D duct is designed specifically for use in bridge crossings and exposed applications. Should be free to move during expansion and contraction. Barrel should be securely clamped.

COMMERCIAL TELEPHONE DUCT

PRODUCT NUMBER DESCRIPTION O.D. WALL WEIGHT PER FOOT FEET PER LIFT
18432 4 Type C Direct Burial 4.350 0.135 1.333 1260'

Note:
(1) Commercial telephone duct has minimum pipe stiffness of 80 lbs/in

Advantages
  • Superior aging and weathering characteristics
  • Ultraviolet protections
  • Super load bearing
  • Excellent structural strength
  • High impact strength
Features
  • Heat resistant
  • Fire resistant
  • Continuous rigid control
  • Smooth inner wall
  • Smooth transition between joints